Summary: a fire water storage tank is a dedicated tank that stores water for fire sprinklers, standpipes and hydrants when the public supply cannot meet the required flow, pressure or duration. In the United States its design, construction, installation and testing are governed by NFPA 22, Standard for Water Tanks for Private Fire Protection, and its inspection, testing and maintenance by NFPA 25. Required capacity equals the design flow rate in gallons per minute multiplied by the required duration in minutes, plus any hose stream allowance. MMI Tank & Industrial Services builds bolted and welded steel NFPA 22 tanks from Phoenix, Arizona.
What Is a Fire Water Storage Tank?
A fire water storage tank (also called a fire protection tank, fire suppression tank or fire water tank) stores a reserved volume of water for fire protection only. It feeds a fire pump (a suction tank), feeds the system by gravity (an elevated or gravity tank), or in some designs is pressurized. The water is not used for process or domestic supply unless the design keeps the fire reserve untouched.
When Is a Fire Water Tank Required?
- A hydrant flow test shows the public main cannot deliver the sprinkler demand at the required pressure.
- The site has no public water supply, such as rural plants, mines, ranches and remote facilities.
- The insurer (for example under FM Global data sheets) or the authority having jurisdiction (AHJ) requires a dedicated or redundant supply.
- The hazard needs a long duration: high-piled storage, distribution centers, plastics, flammable liquids.
What Does NFPA 22 Require?
NFPA 22 covers the tank itself. Key areas:
| Area | Requirement in practice |
|---|---|
| Materials and construction | Rules for welded steel, bolted steel, factory-coated bolted steel, concrete, fiberglass and other tank types |
| Capacity | Net capacity is measured between the overflow inlet and the discharge outlet level (the anti-vortex plate on suction tanks), not the full shell volume |
| Design loads | Water load, wind, seismic and snow per the referenced codes |
| Freeze protection | Tanks in cold climates must be heated so the water stays above freezing; NFPA 22 sets a minimum water temperature of 42°F (5.6°C) |
| Accessories | Overflow, screened vents, roof and shell manholes, ladders, water level indicators and low-temperature alarms |
| Foundations | Designed for the full tank load with acceptable settlement |
| Testing | Leak and weld testing before acceptance |
Always confirm against the edition of NFPA 22 adopted by your AHJ. See our page on the NFPA 22 standard.
How Do You Size a Fire Water Storage Tank?
Required net capacity (gallons) = design flow (gpm) × duration (minutes)
Design flow combines the sprinkler hydraulic demand and the hose stream allowance. Duration comes from NFPA 13 for sprinklers, NFPA 24 for private mains, insurer data sheets or the AHJ.
| Example demand | Duration | Net capacity |
|---|---|---|
| 500 gpm | 30 min | 15,000 gal |
| 750 gpm | 60 min | 45,000 gal |
| 1,000 gpm | 60 min | 60,000 gal |
| 1,500 gpm | 90 min | 135,000 gal |
| 2,000 gpm | 120 min | 240,000 gal |
These are worked examples, not design values. A licensed fire protection engineer sets the demand. For a fuller walk-through see how much water is needed for fire protection, and for tank dimensions at each capacity see the water storage tank size chart.
Suction Tank vs Gravity Tank
- Suction tank: a ground tank feeding a fire pump. The most common type for new facilities. Needs an anti-vortex plate at the outlet.
- Gravity (elevated) tank: provides pressure by height and needs no pump; less common for new work because of cost and seismic design.
- Pressure tank: a smaller pressurized vessel, used for limited applications.
Bolted vs Welded Fire Water Tanks
| Factor | Bolted steel | Welded steel |
|---|---|---|
| Field time | Shorter; panels assembled on site | Longer; welded and coated in place |
| Coating | Factory-applied | Field-applied |
| Size range | Most fire protection sizes | No practical upper limit |
| Expansion | Rings can be added | Fixed |
| Seams | Sealed; inspect sealant | Welded; no sealant |
Both are recognized by NFPA 22 and FM Global. See welded vs bolted steel tanks.
How Is a Fire Water Tank Inspected and Maintained?
NFPA 25 sets the schedule. Typical items:
- Water level and condition checked routinely, more often without supervised level alarms
- Heating system and water temperature checked during cold weather
- Exterior, supports, ladders and foundation inspected periodically
- Interior inspected at intervals set by NFPA 25 (commonly every five years, more often for tanks without corrosion protection)
- Level and temperature alarms tested
MMI performs tank inspection and repair and recoating for existing fire water tanks.
Freeze Protection in Cold Climates
Tanks in Colorado, northern Arizona, Nevada, Oregon and Washington often need heaters, insulation or both. Heater size is based on the tank surface area, the lowest one-day mean temperature at the site and the required minimum water temperature. Piping, vents and overflows also need protection.
Frequently Asked Questions
What size fire water tank do I need?
Multiply the design flow in gallons per minute by the required duration in minutes. For example, 1,000 gpm for 60 minutes needs 60,000 gallons of net capacity. A fire protection engineer sets the flow and duration.
What standard governs fire water storage tanks?
NFPA 22 governs design and construction of tanks for private fire protection. NFPA 25 governs inspection, testing and maintenance. Insurers such as FM Global may add their own requirements.
Can a fire water tank also store domestic or process water?
Only if the design keeps the fire reserve untouched, for example by setting the domestic outlet above the fire reserve level. The AHJ must accept the arrangement.
Are bolted steel tanks allowed for fire protection?
Yes. NFPA 22 includes bolted steel tanks, and they are widely used for fire protection.
How often must a fire water tank be inspected?
NFPA 25 sets routine level and temperature checks, periodic exterior inspections and an interior inspection, commonly every five years. Check the edition your AHJ uses.
Who builds NFPA 22 fire water tanks in Arizona?
MMI Tank & Industrial Services designs, fabricates and erects NFPA 22 fire protection tanks from Phoenix, Arizona, and is licensed in 11 western states. See fire protection tanks or request a quote.